7.5
CVE-2026-9108
- EPSS 0.11%
- Veröffentlicht 14.07.2026 15:09:37
- Zuletzt bearbeitet 25.08.2026 16:59:52
- Erkennungen
Studio 5000 Logix Designer® – Multiple Vulnerabilities
A path traversal security issue exists within Studio 5000 Logix Designer® due to improper limitation of file paths within ACD project files. The software does not sanitize or validate file names embedded in the ACD file structure during the project opening procedure, allowing path traversal sequences to escape the intended extraction directory. If exploited, an attacker could craft a malicious ACD project file that results in arbitrary files being written to attacker-controlled locations on the file system, potentially leading to code execution.
Daten sind bereitgestellt durch National Vulnerability Database (NVD)
Rockwellautomation ≫ Studio 5000 Logix Designer Version < 32.05
Rockwellautomation ≫ Studio 5000 Logix Designer Version >= 33.00 < 33.04
Rockwellautomation ≫ Studio 5000 Logix Designer Version >= 34.00 < 34.04
Rockwellautomation ≫ Studio 5000 Logix Designer Version >= 35.00 < 35.02
Rockwellautomation ≫ Studio 5000 Logix Designer Version 36.00
VulnDex Vulnerability Enrichment
| Typ | Quelle | Score | Percentile |
|---|---|---|---|
| EPSS | FIRST.org | 0.11% | 0.015 |
| Quelle | Base Score | Exploit Score | Impact Score | Vector String |
|---|---|---|---|---|
| NIST | 7.5 | 0.8 | 6 |
CVSS:3.1/AV:L/AC:H/PR:L/UI:R/S:C/C:H/I:H/A:H
|
| PSIRT@rockwellautomation.com | 5.4 | 0 | 0 |
CVSS:4.0/AV:L/AC:H/AT:P/PR:L/UI:A/VC:H/VI:H/VA:H/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
|
CWE-22 Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal')
The product uses external input to construct a pathname that is intended to identify a file or directory that is located underneath a restricted parent directory, but the product does not properly neutralize special elements within the pathname that can cause the pathname to resolve to a location that is outside of the restricted directory.
https://www.rockwellautomation.com/en-us/trust-center/security-advisories/advisory.SD1783.html