5.3

CVE-2026-59693

A vulnerability has been identified in Desigo DXR2 (All versions < V01.21.233.16-7862), Desigo PXC3 (All versions < V01.21.233.16-7862), Desigo PXC4 (All versions < V02.21.194.36-2715), Desigo PXC5.E003 (All versions < V02.21.194.36-2715), Desigo PXC5.E24 (All versions < V02.21.194.36-2715), Desigo PXC7 (All versions < V02.21.194.36-2715). The affected devices are vulnerable to a denial-of-service (DoS) vulnerability. An attacker can exploit this issue by sending a malformed BACnet packet, causing the device to stop responding to BACnet queries. Recovery requires a device reset or reboot to restore normal functionality.
Daten sind bereitgestellt durch das CVE Programm von einer CVE Numbering Authority (CNA) (Unstrukturiert).
HerstellerSiemens
≫
Produkt Desigo DXR2
Default Statusunknown
Version 0
Version < V01.21.233.16-7862
Status affected
HerstellerSiemens
≫
Produkt Desigo PXC3
Default Statusunknown
Version 0
Version < V01.21.233.16-7862
Status affected
HerstellerSiemens
≫
Produkt Desigo PXC4
Default Statusunknown
Version 0
Version < V02.21.194.36-2715
Status affected
HerstellerSiemens
≫
Produkt Desigo PXC5.E003
Default Statusunknown
Version 0
Version < V02.21.194.36-2715
Status affected
HerstellerSiemens
≫
Produkt Desigo PXC5.E24
Default Statusunknown
Version 0
Version < V02.21.194.36-2715
Status affected
HerstellerSiemens
≫
Produkt Desigo PXC7
Default Statusunknown
Version 0
Version < V02.21.194.36-2715
Status affected
VulnDex Vulnerability Enrichment
Diese Information steht angemeldeten Benutzern zur Verfügung. Login Login
Zu dieser CVE wurde keine Warnung gefunden.
EPSS Metriken
Typ Quelle Score Percentile
EPSS FIRST.org 0.16% 0.06
CVSS Metriken
Quelle Base Score Exploit Score Impact Score Vector String
Siemens 5.3 0 0
CVSS:4.0/AV:A/AC:L/AT:N/PR:N/UI:N/VC:N/VI:N/VA:L/SC:N/SI:N/SA:N/E:X/CR:X/IR:X/AR:X/MAV:X/MAC:X/MAT:X/MPR:X/MUI:X/MVC:X/MVI:X/MVA:X/MSC:X/MSI:X/MSA:X/S:X/AU:X/R:X/V:X/RE:X/U:X
Siemens 4.3 2.8 1.4
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:L
CWE-754 Improper Check for Unusual or Exceptional Conditions

The product does not check or incorrectly checks for unusual or exceptional conditions that are not expected to occur frequently during day to day operation of the product.

https://cert-portal.siemens.com/productcert/html/ssa-781903.html