7.5

CVE-2022-31204

Omron CS series, CJ series, and CP series PLCs through 2022-05-18 use cleartext passwords. They feature a UM Protection setting that allows users or system integrators to configure a password in order to restrict sensitive engineering operations (such as project/logic uploads and downloads). This password is set using the OMRON FINS command Program Area Protect and unset using the command Program Area Protect Clear, both of which are transmitted in cleartext.
Daten sind bereitgestellt durch National Vulnerability Database (NVD)
Omron ≫ Sysmac Cs1 Firmware Version < 4.1
   Omron ≫ Sysmac Cs1 Version -
Omron ≫ Sysmac Cj2m Firmware Version < 2.1
   Omron ≫ Sysmac Cj2m Version -
Omron ≫ Sysmac Cj2h Firmware Version < 1.5
   Omron ≫ Sysmac Cj2h Version -
Omron ≫ Sysmac Cp1e Firmware Version < 1.30
   Omron ≫ Sysmac Cp1e Version -
Omron ≫ Sysmac Cp1h Firmware Version < 1.30
   Omron ≫ Sysmac Cp1h Version -
Omron ≫ Sysmac Cp1l Firmware Version < 1.10
   Omron ≫ Sysmac Cp1l Version -
Omron ≫ Cp1w-cif41 Firmware Version -
   Omron ≫ Cp1w-cif41 Version -
Omron ≫ Cx-programmer Version < 9.6
Zu dieser CVE wurde keine Warnung gefunden.
EPSS Metriken
Typ Quelle Score Percentile
EPSS FIRST.org 0.62% 0.465
CVSS Metriken
Quelle Base Score Exploit Score Impact Score Vector String
NIST 7.5 3.9 3.6
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:N/A:N
CWE-319 Cleartext Transmission of Sensitive Information

The product transmits sensitive or security-critical data in cleartext in a communication channel that can be sniffed by unauthorized actors.

https://www.forescout.com/blog/
Third Party Advisory
https://www.cisa.gov/uscert/ics/advisories/icsa-22-179-02
Third Party Advisory
US Government Resource