7.5

CVE-2021-37205

A vulnerability has been identified in SIMATIC Drive Controller family (All versions >= V2.9.2 < V2.9.4), SIMATIC ET 200SP Open Controller CPU 1515SP PC2 (incl. SIPLUS variants) (All versions >= V21.9 < V21.9.4), SIMATIC S7-1200 CPU family (incl. SIPLUS variants) (All versions >= V4.5.0 < V4.5.2), SIMATIC S7-1500 CPU family (incl. related ET200 CPUs and SIPLUS variants) (All versions >= V2.9.2 < V2.9.4), SIMATIC S7-1500 Software Controller (All versions >= V21.9 < V21.9.4), SIMATIC S7-PLCSIM Advanced (All versions >= V4.0 < V4.0 SP1), SIPLUS TIM 1531 IRC (All versions < V2.3.6), TIM 1531 IRC (All versions < V2.3.6). An unauthenticated attacker could cause a denial-of-service condition in a PLC when sending specially prepared packets over port 102/tcp. A restart of the affected device is needed to restore normal operations.

Daten sind bereitgestellt durch National Vulnerability Database (NVD)
SiemensTim 1531 Irc Firmware Version >= 2.2
   SiemensTim 1531 Irc Version-
SiemensSimatic S7-1200 Cpu 1211c Firmware Version >= 4.5.0 < 4.5.2
SiemensSimatic S7-1200 Cpu 1212c Firmware Version >= 4.5.0 < 4.5.2
SiemensSimatic S7-1200 Cpu 1212fc Firmware Version >= 4.5.0 < 4.5.2
SiemensSimatic S7-1200 Cpu 1214fc Firmware Version >= 4.5.0 < 4.5.2
SiemensSimatic S7-1200 Cpu 1214c Firmware Version >= 4.5.0 < 4.5.2
SiemensSimatic S7-1200 Cpu 1215fc Firmware Version >= 4.5.0 < 4.5.2
SiemensSimatic S7-1200 Cpu 1215c Firmware Version >= 4.5.0 < 4.5.2
SiemensSimatic S7-1200 Cpu 1217c Firmware Version >= 4.5.0 < 4.5.2
SiemensSimatic S7-1500 Cpu 1510sp Firmware Version >= 2.9.2 < 2.9.4
SiemensSimatic S7-1500 Cpu 1511-1 Firmware Version >= 2.9.2 < 2.9.4
SiemensSimatic S7-1500 Cpu 1511c-1 Firmware Version >= 2.9.2 < 2.9.4
SiemensSimatic S7-1500 Cpu 1511f-1 Firmware Version >= 2.9.2 < 2.9.4
SiemensSimatic S7-1500 Cpu 1511t-1 Firmware Version >= 2.9.2 < 2.9.4
SiemensSimatic S7-1500 Cpu 1512c-1 Firmware Version >= 2.9.2 < 2.9.4
SiemensSimatic S7-1500 Cpu 1513-1 Firmware Version >= 2.9.2 < 2.9.4
SiemensSimatic S7-1500 Cpu 1513f-1 Firmware Version >= 2.9.2 < 2.9.4
SiemensSimatic S7-1500 Cpu 1513r-1 Firmware Version >= 2.9.2 < 2.9.4
SiemensSimatic S7-1500 Cpu 1515-2 Firmware Version >= 2.9.2 < 2.9.4
SiemensSimatic S7-1500 Cpu 1515f-2 Firmware Version >= 2.9.2 < 2.9.4
SiemensSimatic S7-1500 Cpu 1515r-2 Firmware Version >= 2.9.2 < 2.9.4
SiemensSimatic S7-1500 Cpu 1515t-2 Firmware Version >= 2.9.2 < 2.9.4
SiemensSimatic S7-1500 Cpu 1516-3 Firmware Version >= 2.9.2 < 2.9.4
SiemensSimatic S7-1500 Cpu 1516f-3 Firmware Version >= 2.9.2 < 2.9.4
SiemensSimatic S7-1500 Cpu 1516t-3 Firmware Version >= 2.9.2 < 2.9.4
SiemensSimatic S7-1500 Cpu 1517-3 Firmware Version >= 2.9.2 < 2.9.4
SiemensSimatic S7-1500 Cpu 1517f-3 Firmware Version >= 2.9.2 < 2.9.4
SiemensSimatic S7-1500 Cpu 1518-4 Firmware Version >= 2.9.2 < 2.9.4
SiemensSimatic S7-1500 Cpu 1518f-4 Firmware Version >= 2.9.2 < 2.9.4
SiemensSimatic S7-1500 Cpu 1518t-4 Firmware Version >= 2.9.2 < 2.9.4
Zu dieser CVE wurde keine CISA KEV oder CERT.AT-Warnung gefunden.
EPSS Metriken
Typ Quelle Score Percentile
EPSS FIRST.org 1.14% 0.772
CVSS Metriken
Quelle Base Score Exploit Score Impact Score Vector String
nvd@nist.gov 7.1 8.6 6.9
AV:N/AC:M/Au:N/C:N/I:N/A:C
nvd@nist.gov 7.5 3.9 3.6
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
productcert@siemens.com 7.5 3.9 3.6
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
CWE-401 Missing Release of Memory after Effective Lifetime

The product does not sufficiently track and release allocated memory after it has been used, which slowly consumes remaining memory.