7.5
CVE-2021-35533
- EPSS 0.55%
- Veröffentlicht 26.11.2021 17:15:07
- Zuletzt bearbeitet 21.11.2024 06:12:27
- Quelle cybersecurity@hitachienergy.co
- CVE-Watchlists
- Unerledigt
Improper Input Validation vulnerability in the APDU parser in the Bidirectional Communication Interface (BCI) IEC 60870-5-104 function of Hitachi Energy RTU500 series allows an attacker to cause the receiving RTU500 CMU of which the BCI is enabled to reboot when receiving a specially crafted message. By default, BCI IEC 60870-5-104 function is disabled (not configured). This issue affects: Hitachi Energy RTU500 series CMU Firmware version 12.0.* (all versions); CMU Firmware version 12.2.* (all versions); CMU Firmware version 12.4.* (all versions).
Daten sind bereitgestellt durch National Vulnerability Database (NVD)
Hitachienergy ≫ Rtu500 Firmware Version12.0
Hitachienergy ≫ Rtu500 Firmware Version12.2
Hitachienergy ≫ Rtu500 Firmware Version12.4
| Typ | Quelle | Score | Percentile |
|---|---|---|---|
| EPSS | FIRST.org | 0.55% | 0.671 |
| Quelle | Base Score | Exploit Score | Impact Score | Vector String |
|---|---|---|---|---|
| nvd@nist.gov | 7.5 | 3.9 | 3.6 |
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
|
| nvd@nist.gov | 7.1 | 8.6 | 6.9 |
AV:N/AC:M/Au:N/C:N/I:N/A:C
|
| cybersecurity@hitachienergy.com | 7.5 | 3.9 | 3.6 |
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
|
CWE-20 Improper Input Validation
The product receives input or data, but it does not validate or incorrectly validates that the input has the properties that are required to process the data safely and correctly.