8.6

CVE-2020-24685

An unauthenticated specially crafted packet sent by an attacker over the network will cause a denial-of-service (DoS) vulnerability. Vulnerability allows attacker to stop the PLC. After stopping (ERR LED flashing red), physical access to the PLC is required in order to restart the application. This issue affects: ABB AC500 V2 products with onboard Ethernet version 2.8.4 and prior versions.

Data is provided by the National Vulnerability Database (NVD)
AbbAc500 Cpu Firmware Version < 2.8.5
   AbbPm573-eth Version2.0
   AbbPm583-eth Version2.0
Zu dieser CVE wurde keine CISA KEV oder CERT.AT-Warnung gefunden.
EPSS Metriken
Type Source Score Percentile
EPSS FIRST.org 0.8% 0.719
CVSS Metriken
Source Base Score Exploit Score Impact Score Vector string
nvd@nist.gov 8.6 3.9 4
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H
nvd@nist.gov 5 10 2.9
AV:N/AC:L/Au:N/C:N/I:N/A:P
cybersecurity@ch.abb.com 8.6 3.9 4
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H
CWE-770 Allocation of Resources Without Limits or Throttling

The product allocates a reusable resource or group of resources on behalf of an actor without imposing any restrictions on the size or number of resources that can be allocated, in violation of the intended security policy for that actor.

CWE-789 Memory Allocation with Excessive Size Value

The product allocates memory based on an untrusted, large size value, but it does not ensure that the size is within expected limits, allowing arbitrary amounts of memory to be allocated.