7.8
CVE-2019-19279
- EPSS 0.27%
- Veröffentlicht 10.03.2020 20:15:18
- Zuletzt bearbeitet 21.11.2024 04:34:29
- Quelle productcert@siemens.com
- Teams Watchlist Login
- Unerledigt Login
A vulnerability has been identified in SIPROTEC 4 and SIPROTEC Compact relays equipped with EN100 Ethernet communication modules (All versions). Specially crafted packets sent to port 50000/UDP of the EN100 Ethernet communication modules could cause a Denial-of-Service of the affected device. A manual reboot is required to recover the service of the device. At the time of advisory publication no public exploitation of this security vulnerability was known to Siemens.
Daten sind bereitgestellt durch National Vulnerability Database (NVD)
Zu dieser CVE wurde keine CISA KEV oder CERT.AT-Warnung gefunden.
Typ | Quelle | Score | Percentile |
---|---|---|---|
EPSS | FIRST.org | 0.27% | 0.501 |
Quelle | Base Score | Exploit Score | Impact Score | Vector String |
---|---|---|---|---|
nvd@nist.gov | 7.5 | 3.9 | 3.6 |
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:N/A:H
|
nvd@nist.gov | 7.8 | 10 | 6.9 |
AV:N/AC:L/Au:N/C:N/I:N/A:C
|
CWE-20 Improper Input Validation
The product receives input or data, but it does not validate or incorrectly validates that the input has the properties that are required to process the data safely and correctly.