7.5
CVE-2018-4838
- EPSS 0.25%
- Veröffentlicht 08.03.2018 17:29:00
- Zuletzt bearbeitet 21.11.2024 04:07:33
- Quelle productcert@siemens.com
- Teams Watchlist Login
- Unerledigt Login
A vulnerability has been identified in EN100 Ethernet module IEC 61850 variant (All versions < V4.30), EN100 Ethernet module DNP3 variant (All versions < V1.04), EN100 Ethernet module PROFINET IO variant (All versions), EN100 Ethernet module Modbus TCP variant (All versions), EN100 Ethernet module IEC 104 variant (All versions < V1.22). The web interface (TCP/80) of affected devices allows an unauthenticated user to upgrade or downgrade the firmware of the device, including to older versions with known vulnerabilities.
Daten sind bereitgestellt durch National Vulnerability Database (NVD)
Siemens ≫ En100 Ethernet Module Iec 104 Firmware Version-
Siemens ≫ En100 Ethernet Module Dnp3 Firmware Version-
Siemens ≫ En100 Ethernet Module Modbus Tcp Firmware Version-
Siemens ≫ En100 Ethernet Module Iec 61850 Firmware Version < 4.30
Zu dieser CVE wurde keine CISA KEV oder CERT.AT-Warnung gefunden.
Typ | Quelle | Score | Percentile |
---|---|---|---|
EPSS | FIRST.org | 0.25% | 0.458 |
Quelle | Base Score | Exploit Score | Impact Score | Vector String |
---|---|---|---|---|
nvd@nist.gov | 7.5 | 3.9 | 3.6 |
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N
|
nvd@nist.gov | 5 | 10 | 2.9 |
AV:N/AC:L/Au:N/C:N/I:P/A:N
|
CWE-306 Missing Authentication for Critical Function
The product does not perform any authentication for functionality that requires a provable user identity or consumes a significant amount of resources.