CVE-2018-17924

Rockwell Automation MicroLogix 1400 Controllers and 1756 ControlLogix Communications Modules An unauthenticated, remote threat actor could send a CIP connection request to an affected device, and upon successful connection, send a new IP configuration to the affected device even if the controller in the system is set to Hard RUN mode. When the affected device accepts this new IP configuration, a loss of communication occurs between the device and the rest of the system as the system traffic is still attempting to communicate with the device via the overwritten IP address.

Data is provided by the National Vulnerability Database (NVD)
Zu dieser CVE wurde keine CISA KEV oder CERT.AT-Warnung gefunden.
EPSS Metriken
Type Source Score Percentile
EPSS FIRST.org 0.12% 0.313
CVSS Metriken
Source Base Score Exploit Score Impact Score Vector string
nvd@nist.gov 8.6 3.9 4
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:C/C:N/I:N/A:H
nvd@nist.gov 7.8 10 6.9
AV:N/AC:L/Au:N/C:N/I:N/A:C
CWE-306 Missing Authentication for Critical Function

The product does not perform any authentication for functionality that requires a provable user identity or consumes a significant amount of resources.