10
CVE-2018-16158
- EPSS 70.81%
- Veröffentlicht 30.08.2018 05:29:00
- Zuletzt bearbeitet 21.11.2024 03:52:11
- Quelle cve@mitre.org
- CVE-Watchlists
- Unerledigt
Eaton Power Xpert Meter 4000, 6000, and 8000 devices before 13.4.0.10 have a single SSH private key across different customers' installations and do not properly restrict access to this key, which makes it easier for remote attackers to perform SSH logins (to uid 0) via the PubkeyAuthentication option.
Daten sind bereitgestellt durch National Vulnerability Database (NVD)
Eaton ≫ Power Xpert Meter 4000 Firmware Version < 13.4.0.10
Eaton ≫ Power Xpert Meter 6000 Firmware Version < 13.4.0.10
Eaton ≫ Power Xpert Meter 8000 Firmware Version < 13.4.0.10
| Typ | Quelle | Score | Percentile |
|---|---|---|---|
| EPSS | FIRST.org | 70.81% | 0.986 |
| Quelle | Base Score | Exploit Score | Impact Score | Vector String |
|---|---|---|---|---|
| nvd@nist.gov | 9.8 | 3.9 | 5.9 |
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
|
| nvd@nist.gov | 10 | 10 | 10 |
AV:N/AC:L/Au:N/C:C/I:C/A:C
|
CWE-798 Use of Hard-coded Credentials
The product contains hard-coded credentials, such as a password or cryptographic key.