10
CVE-2017-13997
- EPSS 1.59%
- Published 03.10.2017 01:29:01
- Last modified 20.04.2025 01:37:25
- Source ics-cert@hq.dhs.gov
- Teams watchlist Login
- Open Login
A Missing Authentication for Critical Function issue was discovered in Schneider Electric InduSoft Web Studio v8.0 SP2 or prior, and InTouch Machine Edition v8.0 SP2 or prior. InduSoft Web Studio provides the capability for an HMI client to trigger script execution on the server for the purposes of performing customized calculations or actions. A remote malicious entity could bypass the server authentication and trigger the execution of an arbitrary command. The command is executed under high privileges and could lead to a complete compromise of the server.
Data is provided by the National Vulnerability Database (NVD)
Schneider-electric ≫ Wonderware Indusoft Web Studio Updatesp2 Version <= 8.0
Schneider-electric ≫ Wonderware Intouch Updatesp2 SwEditionmachine Version <= 8.0
Zu dieser CVE wurde keine CISA KEV oder CERT.AT-Warnung gefunden.
Type | Source | Score | Percentile |
---|---|---|---|
EPSS | FIRST.org | 1.59% | 0.808 |
Source | Base Score | Exploit Score | Impact Score | Vector string |
---|---|---|---|---|
nvd@nist.gov | 9.8 | 3.9 | 5.9 |
CVSS:3.0/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
|
nvd@nist.gov | 10 | 10 | 10 |
AV:N/AC:L/Au:N/C:C/I:C/A:C
|
CWE-306 Missing Authentication for Critical Function
The product does not perform any authentication for functionality that requires a provable user identity or consumes a significant amount of resources.