7.8

CVE-2015-5374

A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. Specially crafted packets sent to port 50000/UDP could cause a denial-of-service of the affected device. A manual reboot may be required to recover the service of the device.

Data is provided by the National Vulnerability Database (NVD)
SiemensSiprotec Firmware Version4.24
Zu dieser CVE wurde keine CISA KEV oder CERT.AT-Warnung gefunden.
EPSS Metriken
Type Source Score Percentile
EPSS FIRST.org 84.83% 0.993
CVSS Metriken
Source Base Score Exploit Score Impact Score Vector string
nvd@nist.gov 7.8 10 6.9
AV:N/AC:L/Au:N/C:N/I:N/A:C