A vulnerability has been identified in Firmware variant PROFINET IO for EN100 Ethernet module : All versions < V1.04.01; Firmware variant Modbus TCP for EN100 Ethernet module : All versions < V1.11.00; Firmware variant DNP3 TCP for EN100 Ethernet module : All versions < V1.03; Firmware variant IEC 104 for EN100 Ethernet module : All versions < V1.21; EN100 Ethernet module included in SIPROTEC Merging Unit 6MU80 : All versions < 1.02.02. Specially crafted packets sent to port 50000/UDP could cause a denial-of-service of the affected device. A manual reboot may be required to recover the service of the device.
Daten sind bereitgestellt durch National Vulnerability Database (NVD)
Siemens ≫ Siprotec Firmware Version4.24
| Typ | Quelle | Score | Percentile |
|---|---|---|---|
| EPSS | FIRST.org | 74.32% | 0.994 |
| Quelle | Base Score | Exploit Score | Impact Score | Vector String |
|---|---|---|---|---|
| nvd@nist.gov | 7.8 | 10 | 6.9 |
AV:N/AC:L/Au:N/C:N/I:N/A:C
|