7.8

CVE-2011-4878

Directory traversal vulnerability in miniweb.exe in the HMI web server in Siemens WinCC flexible 2004, 2005, 2007, and 2008 before SP3; WinCC V11 (aka TIA portal) before SP2 Update 1; the TP, OP, MP, Comfort Panels, and Mobile Panels SIMATIC HMI panels; WinCC V11 Runtime Advanced; and WinCC flexible Runtime allows remote attackers to read arbitrary files via a ..%5c (dot dot backslash) in a URI.

Data is provided by the National Vulnerability Database (NVD)
SiemensWincc Flexible Version2004
SiemensWincc Flexible Version2005
SiemensWincc Flexible Version2007
SiemensWincc Flexible Version2008
SiemensWincc Flexible Version2008 Updatesp1
SiemensWincc Flexible Version2008 Updatesp2
SiemensWincc Updatesp2 Version <= v11
SiemensWincc Versionv11
SiemensWincc Versionv11 Updatesp1
SiemensSimatic Hmi Panels Versioncomfort_panels
SiemensSimatic Hmi Panels Versionmobile_panels
SiemensSimatic Hmi Panels Versionmp
SiemensSimatic Hmi Panels Versionop
SiemensSimatic Hmi Panels Versiontp
Zu dieser CVE wurde keine CISA KEV oder CERT.AT-Warnung gefunden.
EPSS Metriken
Type Source Score Percentile
EPSS FIRST.org 24.16% 0.959
CVSS Metriken
Source Base Score Exploit Score Impact Score Vector string
nvd@nist.gov 7.8 10 6.9
AV:N/AC:L/Au:N/C:C/I:N/A:N
CWE-22 Improper Limitation of a Pathname to a Restricted Directory ('Path Traversal')

The product uses external input to construct a pathname that is intended to identify a file or directory that is located underneath a restricted parent directory, but the product does not properly neutralize special elements within the pathname that can cause the pathname to resolve to a location that is outside of the restricted directory.