9.8

CVE-2022-41688

Delta Electronics InfraSuite Device Master versions 00.00.01a and prior lack proper authentication for functions that create and modify user groups. An attacker could provide malicious serialized objects that could run these functions without authentication to create a new user and add them to the administrator group.

Daten sind bereitgestellt durch National Vulnerability Database (NVD)
DeltawwInfrasuite Device Master Version < 00.00.02a
Zu dieser CVE wurde keine CISA KEV oder CERT.AT-Warnung gefunden.
EPSS Metriken
Typ Quelle Score Percentile
EPSS FIRST.org 0.21% 0.429
CVSS Metriken
Quelle Base Score Exploit Score Impact Score Vector String
nvd@nist.gov 7.5 3.9 3.6
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:N/I:H/A:N
ics-cert@hq.dhs.gov 9.8 3.9 5.9
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
CWE-306 Missing Authentication for Critical Function

The product does not perform any authentication for functionality that requires a provable user identity or consumes a significant amount of resources.