Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 have an insecure permissions setting on the user.token field that is accessible to everyone through the /cgi/get_param.cgi HTTP API. This leads to disclosing active session ids of currently logged-in administrators. The session id can then be reused to act as the administrator, allowing reading of the cleartext password, or reconfiguring the device.
Daten sind bereitgestellt durch National Vulnerability Database (NVD)
PowertekpdusBasic Pdu Firmware Version < 3.30.30
   PowertekpdusBasic Pdu Version-
PowertekpdusPm Pdu Firmware Version < 3.30.30
   PowertekpdusPm Pdu Version-
PowertekpdusPiml Pdu Firmware Version < 3.30.30
   PowertekpdusPiml Pdu Version-
PowertekpdusSmart Pim Firmware Version < 3.30.30
   PowertekpdusSmart Pim Version-
PowertekpdusSmart Pos Firmware Version < 3.30.30
   PowertekpdusSmart Pos Version-
PowertekpdusSmart Pom Firmware Version < 3.30.30
   PowertekpdusSmart Pom Version-
PowertekpdusSmart Poms Firmware Version < 3.30.30
   PowertekpdusSmart Poms Version-
Zu dieser CVE wurde keine CISA KEV oder CERT.AT-Warnung gefunden.
EPSS Metriken
Typ Quelle Score Percentile
EPSS FIRST.org 0.58% 0.684
CVSS Metriken
Quelle Base Score Exploit Score Impact Score Vector String
nvd@nist.gov 9.8 3.9 5.9
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
nvd@nist.gov 7.5 10 6.4
AV:N/AC:L/Au:N/C:P/I:P/A:P
cve@mitre.org 9.8 3.9 5.9
CVSS:3.1/AV:N/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:H
CWE-732 Incorrect Permission Assignment for Critical Resource

The product specifies permissions for a security-critical resource in a way that allows that resource to be read or modified by unintended actors.