8.1
CVE-2022-30319
- EPSS 0.06%
- Published 28.07.2022 16:15:11
- Last modified 21.11.2024 07:02:34
- Source cve@mitre.org
- Teams watchlist Login
- Open Login
Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.
Data is provided by the National Vulnerability Database (NVD)
Honeywell ≫ Saia Pg5 Controls Suite Version-
Zu dieser CVE wurde keine CISA KEV oder CERT.AT-Warnung gefunden.
Type | Source | Score | Percentile |
---|---|---|---|
EPSS | FIRST.org | 0.06% | 0.183 |
Source | Base Score | Exploit Score | Impact Score | Vector string |
---|---|---|---|---|
nvd@nist.gov | 8.1 | 2.8 | 5.2 |
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N
|
CWE-290 Authentication Bypass by Spoofing
This attack-focused weakness is caused by incorrectly implemented authentication schemes that are subject to spoofing attacks.