8.1

CVE-2022-30319

Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.
Daten sind bereitgestellt durch National Vulnerability Database (NVD)
Zu dieser CVE wurde keine Warnung gefunden.
EPSS Metriken
Typ Quelle Score Percentile
EPSS FIRST.org 0.06% 0.183
CVSS Metriken
Quelle Base Score Exploit Score Impact Score Vector String
nvd@nist.gov 8.1 2.8 5.2
CVSS:3.1/AV:A/AC:L/PR:N/UI:N/S:U/C:H/I:H/A:N
CWE-290 Authentication Bypass by Spoofing

This attack-focused weakness is caused by incorrectly implemented authentication schemes that are subject to spoofing attacks.